New power in energy! | Installation Cables and Flexible Cables

NYM ( NVV )

NYM ( NVV )

Construction
1
Conductor: Single or Stranded Wire Copper
2
Isolate: PVC Insulation
3
Filling: Polyethylene or PVC Filler
4
Outer Case: PVC Outer Sheath
Application Areas

It is suitable for use in damp environments, flush-mounted and surface-mounted fixed installations. It can also be used in open installations outside the building, but underground use is not recommended.

Standards
  •  TS 9759
  •  VDE 0250
Technical Specifications

Min. bending radius

10 x D

Max. operating temperature 70°
Max. short-circuit temperature 160°
Rated voltage Uo/U 300/500 V
Test voltage 2 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Size and Weights  
Electrical Information
Nominal Cross-Section
Approximate Outer Diameter Approximate Net Weight Standard Shipment DC Conductor Resistance at 20°C (Max.) Current Carrying Capacity
mm²
mm
kg/km
length/m
ohm/km
Air
2x1.5 re
8.80
105
100
12.1
22
2x2.5 re
10.0
145
100
7.41
30
2x4 re
11.0
195
100
4.61
40
2x6 re
12.0
250
100
3.08
50
2x10 rm
16.0
420
100
1.83
70
2x16 rm
18.0
590
1000
1.15
93
2x25 rm
21.0
860
1000
0.727
108
2x35 rm
23.0
1150
1000
0.524
135
3x1.5 re
9.0
125
100
12.1
22
3x2.5 re
10.5
175
100
7.41
30
3x4 re
11.5
240
100
4.61
40
3x6 re
13.0
325
100
3.08
50
3x10 rm
16.5
520
100
1.83
70
3x16 rm
19.0
740
1000
1.15
93
3x25 rm
22.0
1100
1000
0.727
108
3x35 rm
25.0
1460
1000
0.524
135
4x1.5 re
10.0
145
100
12.1
18
4x2.5 re
11.5
215
100
7.41
24
4x4 re
13.0
290
100
4.61
35
4x6 re
14.5
375
100
3.08
45
4x10 rm
18.5
620
100
1.83
70