New power in energy! | Installation Cables and Flexible Cables

H07VVH6-F ( FLAT )

H07VVH6-F ( FLAT )

Construction
1
Conductor: Single or Multi-Stranded Copper
2
Filling: PVC Insulation
3
Outer Case: PVC Outer Sheath
Application Areas

These cables are used as power and control cables in enclosed spaces where mechanical stresses are low, in moving environments, conveyor systems, lifting equipment, cranes and container bridges, as well as in racking system floor channels.

Standards
  •  IEC 60227-6
Technical Specifications

Min. bending radius

8 x D

Max. operating temperature 70°
Max. short-circuit temperature 160°
Rated voltage Uo/U 450/750 V
Test voltage 2.5 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Nominal Cross-Section mm2 Approximate Outer Diameter mm Approximate Net Weight kg/km Conductor Resistance Max. ohm/km (20°C) Current Carrying Capacity
3x1.5 * 5.8x13.0 138 13.3 20
3x2.5 * 6.3x14.0 176 7.98 27
3x4 * 7.5x17.0 262 4.95 34
3x6 * 7.9x18.5 327 3.30 48
3x10 * 8.8x22.0 474 1.91 66
3x16 * 10.3x25.5 690 1.21 89
3x25 * 12.4x33.0 1060 0.780 118
3x35 13.5x34.5 1344 0.554 145
3x50 16.7x36.7 1844 0.386 176
3x70 21.0x48.0 2794 0.272 224
3x95 21.8x55.8 3541 0.206 271
4x1.5 * 5.8x14.4 160 13.3 20
4x2.5 * 6.4x18.0 231 7.98 27
4x4 * 6.5x20.2 294 4.95 34
4x6 * 7.1x22.4 386 3.30 48
4x10 * 9.0x28.0 623 1.91 66
4x16 * 11.0x33.7 950 1.21 89
4x25 * 12.9x40.7 1384 0.780 118
4x35 15.0x45.0 1869 0.554 145
4x50 17.0x52.8 2574 0.386 176
4x70 21.0x61.0 3635 0.272 224
3x16+10 11.0x33.7 899 1.21/1.91 89
3x25+16 13.4x38.2 1293 0.780/1.21 118
3x35+16 15.0x42.5 1659 0.554/1.21 145