New power in energy! | Installation Cables and Flexible Cables

H05VV-F / TTR / IEC 71C

H05VV-F / TTR / IEC 71C

Construction
1
Conductor: Multi-Stranded Copper
2
Isolate: PVC Insulation
3
Outer Case: PVC Outer Sheath
Application Areas

Suitable for use in internal and external areas without excessive mechanical stress, underground and in cable ducts.

Standards
  •  TS EN 50525-2-11
  •  BS EN 50525-2-11
  •  DIN EN 50525-2-11
Technical Specifications

Min. bending radius

If D≤12, then 5D - If D>12, then 6D

Max. operating temperature 60°
Max. short-circuit temperature 150°
Rated voltage 300/500 V
Test voltage 2 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Size and Weights
  Electrical Information
Nominal Cross-Section Approx. Outer Diameter Approx. Net Weight Standard Delivery Conductor DC Resistance at 20°C (Max.)
 
In Air (A)
mm²
mm
kg/km length/m ohm/km
2x0.75
6.5
58
100
26.0
6
2x1
7.0
65
100
19.5
10
2x1.5
7.7
82
100
13.3
16
2x2.5
9.6
130
100
7.98
25
2x4
11.5
182
100
4.95
32
3x0.75
6.4
63
100
26.0
6
3x1
7.1
74
100
19.5
10
3x1.5
7.9
103
100
13.3
16
3x2.5
9.8
159
100
7.98
25
3x4
11.6
230
100
4.95
32
5x0.75
7.9
100
100
26.0
6
5x4
14.5
380
100
4.95
32