New power in energy! | Halogen Free Fire Resistant Cables

NHXMH FE 180 ( 052XZ1-U FE 180 )

NHXMH FE 180 ( 052XZ1-U FE 180 )

TSHD 604 | VDE 0276

Construction
1
Conductor: Single or Stranded Copper Wire
2
Tape: Mica Tape
3
Isolate: XLPE Insulation
4
:
5
:
Application Areas

These cables are used to provide safe energy transmission indoors and outdoors in a variety of areas such as schools, hospitals, meeting rooms and shopping centers. Their durable construction is designed to meet the requirements in different environments, providing a solution that is both reliable and efficient.

Standards
  •  VDE 276-604
  •  VDE 266
  •  TS HD 604 S1
Technical Specifications
Min. bending radius 18 x D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Low smoke density EN 61034
Halogen-free EN 60754 - EN 50267
Circuit integrity IEC 60331-21
Bundled cable vertical flame propagation test EN 60332-3-24
Lead-free  ̶P̶b̶
Technical Data
Dimensions and Weights Electrical Information
 
Nominal Cross-Section
 
Approximate Outer Diameter
 
Approximate Net Weight
1000 m
Shipping Reel Dimensions
for Cable
At 20 °C
Conductor DC Resistance
(Max.)
Current Carrying Capacity
  In Air (A)
mm² mm kg/km cm ohm/km  
1x4 re 7,5 90 70 4,61 56 40
1x6 re 8,0 110 70 3,08 71 53
1x10 rm 9,5 160 80 1,83 100 74
1x16 rm 10,0 220 80 1,15 135 100
1x25 rm 11,5 320 90 0,727 180 133
1x35 rm 12,5 420 90 0,524 225 167
1x50 rm 14,0 530 90 0,387 273 205
1x70 rm 16,0 740 110 0,268 350 265
1x95 rm 17,5 950 110 0,193 428 325
1x120 rm 19,0 1200 120 0,153 495 380
1x150 rm 21,0 1450 130 0,124 575 442
1x185 rm 23,0 1850 140 0,0991 660 510
1x240 rm 25,5 2350 160 0,0754 780 605
1x300 rm 28,5 3000 200 0,0601 864 690
1x400 rm 32,0 3900 220 0,0470 1018 810
1x500 rm 35,5 4900 240 0,0366 1173 930