New power in energy! | Halogen Free Fire Resistant Cables

N2XH

N2XH

Construction
1
Conductor: Single or Stranded Copper Wire
2
Isolate: XLPE Insulation
3
Filling: HFFR Filler
4
Outer Case: HFFR Outer Sheath
Application Areas

These cables are used to provide reliable power transmission indoors and outdoors in various areas such as schools, hospitals, meeting halls and shopping malls.

Standards
  •  VDE 0276-604
  •  TS HD 604 S1
Technical Specifications
Min. bending radius 12 x D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Low smoke EN 61034-2
Halogen-free EN 60754-1-2
Bundled cable vertical flame propagation test EN 60332-3-24 Cat. C
Lead-free  ̶P̶b̶
Technical Data
Dimensions and Weights
Electrical Information
 
Nominal Section
 
Approximate Outer Diameter
 
Approximate Net Weight
1000 m
Shipping Reel Dimensions
for Cable
20 °C’ at
Conductor DC Resistance

(Max.)
Current Carrying
Capacity
 
In Air (A)
mm² mm kg/km cm ohm/km
3x1.5 re
9.5
135
90
12.1
23
3x2.5 re
10.5
175
90
7.41
32
3x4 re
12.0
240
90
4.61
42
3x6 re
13.0
320
100
3.08
53
3x10 rm
16.0
520
110
1.83
73
3x16 rm
18.0
710
120
1.15
98
3x25 rm
21.5
1040
130
0.727
126
3x35 rm
24.0
1350
140
0.524
156
3x50 rm
27.0
1780
160
0.387
190
3x70 rm
31.5
2500
180
0.268
245
3x95 rm
35.0
3300
200
0.193
297
3x120 rm
39.0
4250
230
0.153
346
3x150 rm
43.5
5100
240
0.124
398
3x185 rm
48.0
6400
200*
0.0991
455
3x240 rm
53.0
8200
220*
0.0754
535
3x300 rm
59.0
10200
240*
0.0601
630
3x400 rm
66.0
13000
240**
0.0470
740