New power in energy! | Halogen Free Fire Resistant Cables

N2XCH

N2XCH

Construction
1
:
2
:
3
:
4
:
5
:
Application Areas

These cables are designed for safe use in energy networks in hotels, schools, high-rise buildings, hospitals, power plants, data processing centers and business centers where there is a risk of fire. Thanks to their construction in compliance with fire safety standards, they increase the safety of energy transmission in these critical areas.

Standards
  •  TS HD 604 S1
  •  DIN VDE 0276
Technical Specifications
Min. bending radius 12 x D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Low smoke density EN 61034-2
Halogen-free EN 60754-1-2
Bundled cable vertical flame propagation test EN 60332-3-24 Cat. C
Lead-free  ̶P̶b̶
Technical Data
Size and Weights Electrical Information
 
Nominal Cross-Section
 
Approximate Outer Diameter
 
Approximate Net Weight
1000 m
Cable Shipping Reel
Dimensions
DC Conductor Resistance at 20 °C
(Max.)
Current Carrying Capacity
 
In Soil (A)
 
In Air (A)
mm²
mm
kg/km
cm
ohm/km
3x1.5 re
13.5
315
100
12.1
30
23
3x2.5 re
14.0
360
100
7.41
40
32
3x4 re
15.5
430
120
4.61
52
42
3x6 re
16.5
520
120
3.08
64
53
3x10 rm
20.0
930
120
1.83
86
73
3x16 rm
22.0
1200
130
1.15
111
98
3x25 rm
26.0
1750
140
0.727
143
126
3x35 rm
28.5
2150
140
0.524
173
156
3x50 rm
31.0
2750
160
0.387
205
190
3x70 rm
36.5
3800
200
0.268
252
245
3x95 rm
40.0
4800
220
0.193
303
297
3x120 rm
44.0
5800
160*
0.153
346
346
3x150 rm
50.0
7300
200*
0.124
390
398
3x185 rm
55.0
9000
220*
0.0991
441
455
3x240 rm
61.0
11000
240*
0.0754
511
535