New power in energy! | Halogen Free Fire Resistant Cables

052XZ1-F

052XZ1-F

Construction
1
Conductor: Twisted Copper Wire
2
Isolate: XLPE Insulation
3
Outer Case: HFFR Outer Sheath
Application Areas

It is used in places with fire risk such as refineries, hotels, schools, tunnels, high-rise buildings, hospitals, power plants, data processing centers and busy business centers.

Standards
  •  TSE K 176
Technical Specifications
Min. bending radius If D≤12, 5D - If D>12, 6D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage 300/500 V
Test voltage 2 kV
Low smoke density EN 61034-2
Halogen-free EN 60754-1-2
Multi-core cable vertical flame propagation test EN 60332-3-24 Cat. C
Lead-free  ̶P̶b̶
Technical Data
Dimensions and Weights Electrical Information
 
    Nominal Section
 
  Approximate Outer Diameter
 
  Approximate Net Weight
1000 m
Shipment Reel Dimensions
for Cable
  20 °C DC Resistance of Conductor (Max.) Current Carrying Capacity
 
In Air (A)
mm² mm kg/km cm ohm/km
2x0.75 6.0 80 100 26.0 14
2x1 6.5 90 100 19.5 17
2x1.5 8.0 105 100 13.3 22
2x2.5 9.0 135 100 7.98 30
2x4 11.0 200 100 4.95 40
2x6 12.0 250 100 3.30 50
2x10 15.0 400 1000 1.91 70
2x16 17.5 550 1000 1.21 93
2x25 21.0 780 1000 0.780 108
2x35 23.0 1050 1000 0.554 135
3x0.75 6.5 90 100 26.0 14
3x1 7.0 100 100 19.5 17
3x1.5 8.5 120 100 13.3 22
3x2.5 9.5 160 100 7.98 30
3x4 11.5 235 100 4.95 40
3x6 13.0 310 100 3.30 50
3x10 16.0 510 1000 1.91 70
3x16 18.0 660 1000 1.21 93
3x25 22.0 1050 1000 0.780 108
3x35 24.5 1400 1000 0.554 135
4x0.75 7.0 100 100 26.0 12
4x1 7.5 120 100 19.5 15
4x1.5 9.0 140 100 13.3 18
4x2.5 10.5 190 100 7.98 24
4x4 13.0 300 100 4.95 32
4x6 15.0 420 100 3.30 42
4x10 17.5 610 1000 1.91 60
4x16 21.0 850 1000 1.21 80
4x25 24.0 1275 1000 0.780 100
4x35 27.0 1670 1000 0.554 124
5x0.75 8.0 130 100 26.0 12
5x1 8.5 150 100 19.5 15
5x1.5 10.0 190 1000 13.3 18
5x2.5 11.0 265 1000 7.98 24
5x4 14.0 410 1000 4.95 32