New power in energy! | Copper Low Voltage Cables

YVZ3V ( NYFGBY )

YVZ3V ( NYFGBY )

Construction
1
Conductor: Single or Stranded Copper Wire
2
Isolate: PVC Insulation
3
Filling: Polyethylene or PVC Filler
4
Armor: Galvanized Flat Steel Wires
5
Tape: Galvanized Steel Strip
6
Outer Case: PVC Outer Sheath
Application Areas

Its resistance to mechanical stress makes it suitable for underground use under severe operating conditions.

Standards
  •  TS IEC 60502-1
  •  IEC 60502-1
  •  VDE 0271
  •  IS 1516.1
Technical Specifications
Min. bending radius

12 x D

Max. operating temperature 70°
Max. short-circuit temperature 160°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Dimensions and Weights
Electrical Information
 
Nominal Section
 
Approximate Outer Diameter
 
Approximate Net Weight
1000 m
Reel Dimensions for Cable
At 20 °C’ (Celsius)
Conductor DC Resistance
(Max.)
Current Carrying Capacity
 
In the Ground (A)
 
In the Air (A)
mm²
mm
kg/km
 cm
ohm/km
3x16 rm
23,5
1220
140
1,15
102
79
3x25 rm
26,5
1700
140
0,727
133
100
3x35 rm
28,5
2060
140
0,524
159
125
3x50 rm
32,0
2600
160
0,387
188
153
3x70 rm
36,5
3450
200
0,268
232
195
3x95 rm
41,0
4500
220
0,193
280
238
3x120 rm
44,0
5500
160*
0,153
318
275
3x150 rm
49,0
6550
200*
0,124
359
320
3x185 rm
53,0
8100
220*
0,0991
406
364
3x240 rm
60,0
10000
240*
0,0754
473
430
3x300 rm
66,0
13000
200**
0,0601
535
510
3x400 rm
74,0
16000
220**
0,0470
613
595