New power in energy! | Copper Low Voltage Cables

YVZ2V ( NYRY )

YVZ2V ( NYRY )

Construction
1
Conductor: Single or Stranded Copper Wire
2
Isolate: PVC Insulation
3
Filling: Polyethylene or PVC Filler
4
Armor: Galvanized Round Steel Wires
5
Outer Case: PVC Outer Sheath
Application Areas

Due to its resistance to mechanical stress, it can be used underground under heavy operating conditions.

Standards
  •  TS IEC 60502-1
  •  IEC 60502-1
  •  IS 1516.1
  •  VDE 0271
Technical Specifications
Min. bending radius 12 x D
Max. operating temperature 70°
Max. short-circuit temperature 160°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Size and Weights Electrical Information
 
    Nominal Cross-section
 
  Approximate Outer Diameter
 
  Approximate Net Weight
1000 m
Shipping Drum Dimensions
For Cable
20°C at
Conductor DC Resistance
(Max.)
Current Carrying Capacity
 
  In Ground (A)
 
  In Air (A)
mm² mm kg/km cm ohm/km
3x1.5 re 14.5 380 100 12.1 27 19
3x2.5 re 16.0 440 100 7.41 36 25
3x4 re 17.0 620 120 4.61 47 34
3x6 re 18.5 720 120 3.08 59 43
3x10 rm 21.0 940 120 1.83 79 59
3x16 rm 24.0 1350 140 1.15 102 79
4x1.5 re 15.0 420 100 12.1 27 19
4x2.5 re 16.5 580 110 7.41 36 25
4x4 re 18.0 750 110 4.61 49 34
4x6 re 19.5 850 120 3.08 59 43
4x10 rm 23.5 1250 120 1.83 79 59
4x16 rm 27.0 1700 140 1.15 102 79
4x25 rm 31.0 2300 160 0.727 133 100
4x35 rm 33.0 2800 180 0.524 159 125
4x50 rm 39.0 3850 210 0.387 188 153
4x70 rm 43.0 4950 220 0.268 232 195
4x95 rm 50.0 6950 180* 0.193 280 238
4x120 rm 54.0 8300 210* 0.153 318 275
4x150 rm 58.0 9750 220* 0.124 359 320
4x185 rm 64.0 11850 230* 0.0991 406 364
4x240 rm 71.0 14850 210* 0.0754 473 430
4x300 rm 79.0 19000 220** 0.0601 535 510
4x400 rm 88.0 23500 230** 0.0470 613 595
5x1.5 re 16.5 575 110 12.1 27 19
5x2.5 re 17.5 650 110 7.41 36 25
5x4 re 20.0 850 120 4.61 47 34
5x6 re 21.0 1010 120 3.08 59 43
5x10 rm 25.0 1525 140 1.83 79 59
5x16 rm 29.0 2010 160 1.15 102 79