New power in energy! | Aluminum Low Voltage Cables

YAXZ3V ( NA2XFGBY )

YAXZ3V ( NA2XFGBY )

Construction
1
Conductor: Aluminum Wire
2
Isolate: PVC Insulation
3
Filling: Polyethylene or PVC Filler
4
Armor: Galvanized Round Steel Wires
5
Outer Case: PVC Outer Sheath
Application Areas

Resistant to mechanical stress and suitable for severe operating conditions, it can be used internally and externally under ground and in cable ducts.

Standards
  •  TS IEC 60502-1
  •  VDE 0271
Technical Data
Dimensions and Weights Electrical Information
 
  Nominal Cross-Section
 
  Approximate Outer Diameter
 
  Net Weight
1000 m
Reel Dimensions for Cable Delivery
  At 20°C Maximum Conductor Resistance   Current Carrying Capacity
(Approx.)
(mm²) (mm) (kg/km) (cm) (ohm/km) In Soil (A)
At 20°C
In Air (A)
At 30°C
3x25/16 rm 25.0 1250 150 1.200 111 100
3x35/16 rm 27.0 1400 160 0.868 132 122
3x50/25 rm 31.0 1800 180 0.641 157 147
3x70/35 rm 35.5 2250 210 0.443 195 189
3x95/50 rm 39.5 2800 230 0.320 233 232
3x120/70 rm 44.0 3400 240 0.253 266 270
3x150/70 rm 48.0 4100 240 0.206 299 308
3x185/95 rm 53.0 4800 250 0.164 340 357
3x240/120 rm 58.0 5900 240* 0.125 401 435
3x300/150 rm 65.0 7300 250* 0.100 455 501
3x400/185 rm 75.0 9200 260* 0.0778 526 592