YAXV ( NA2XY )

YAXV ( NA2XY )

Construction
1
Conductor: Single or Stranded Aluminum
2
Isolate: XLPE Insulation
3
Filling: Polyethylene or PVC Filler
4
Outer Case: PVC Outer Sheath
Application Areas

Designed for use in cable ducts and pipes in power distribution stations, residential and industrial plants. It is preferred in areas where there is no risk of mechanical damage.

Standards
  •  TS IEC 60502-1
  •  IEC 60502-1
  •  VDE 0276
  •  IS 1516.1
Technical Specifications
Min. bending radius 15 x D
Max. operating temperature 90°
Max. short-circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
Test voltage 3.5 kV
Single cable vertical flame propagation test EN 60332-1-2
Lead-free  ̶P̶b̶
Technical Data
Dimensions and Weights Electrical Information
 
  Nominal Cross-Section
 
  Approximate Outer Diameter
 
  Net Weight
1000 m
Reel Dimensions for Cable Delivery
  Maximum Conductor Resistance at 20°C   Current Carrying Capacity (Approx.)
(mm²) (mm) (kg/km) (cm) (ohm/km) In Soil (A) at 20°C In Air (A) at 30°C
3x25/16 rm 23.0 750 140 1.200 111 100
3x35/16 rm 25.0 850 150 0.868 132 122
3x50/25 rm 29.0 1200 160 0.641 157 147
3x70/35 rm 33.0 1550 200 0.443 195 189
3x95/50 rm 37.0 2000 220 0.320 233 232
3x120/70 rm 41.5 2500 230 0.253 266 270
3x150/70 rm 45.0 3000 240 0.206 299 308
3x185/95 rm 51.0 3650 250 0.164 340 357
3x240/120 rm 56.0 4700 230* 0.125 401 435
3x300/150 rm 63.0 5900 240* 0.100 455 501
3x400/185 rm 70.0 7550 250* 0.0778 526 592